Question

A PLC documentation (Omron) shows a correct and incorrect use of Condition Flags (see image). But I do not see any difference between the two: if Instruction A is ON, then both Instruction B and the un-labeled instruction will be executed. Both ladder diagram implies achieve the same thing to me. Why one is incorrect and the other is correct?

enter image description here

Was it helpful?

Solution

This is similar to the differential instruction problem. Again, the condition flag (CF) is global and changes each time, in this case, a comparison operation is executed.

In the incorrect example, Instruction A will perform a comparison and the CF for equals (=) will be either true or false. The implied desired flow of operation is that if the instruction A returns true for equals then execute Instruction B, otherwise continue to the final rung.

In the case where Instruction A returns true for equals, however, then Instruction B will execute and, in this case, it is implied that it too is performing a comparison operation (presumably to be picked up in the next rung). If B returns false for equals, however, then the final branch of the current rung will still execute because it takes place after B's comparison - this even though the intention is to only execute the final branch if A returns false - not B!

The second example (correct) shows how to avoid leaking B's results into A's logic.